Model HMP45C Temperature and Relative Humidity Probe
BeginProg
Scan(1,Sec,1,0)
'HMP45C Temperature & Relative Humidity Sensor measurements AirTC and RH:
SW12 (1 )
Delay(0,150,mSec)
VoltDiff (AirTC,1,mV2500,2,True,0,_60Hz,0.1,-40)
VoltDiff (RH,1,mV2500,1,True,0,_60Hz,0.1,0)
SW12 (0)
If RH>100 And RH<108 Then RH=100
CallTable(Temp_RH)
NextScan
EndProg
CR10(X) Program using Differential Measurement Instructions Using SW12V on Datalogger
;Turn the HMP45C on.
;
01: Do (P86)
1: 41 Set Port 1 High ;Jumper wire from SW12V control to C1
;Orange wire (C1) if older wiring
;Green wire (C1) if using SW12V device
;For CR23X or CR5000 use 49 for SW12V internal
;control port
;Pause 150 mSec before making measurements so the
;probe can stabilize on true readings.
;
02: Excitation with Delay (P22)
1: 1 Ex Channel
2: 0 Delay W/Ex (units = 0.01 sec)
3: 15 Delay After Ex (units = 0.01 sec)
4: 0 mV Excitation
;Measure the HMP45C temperature.
;
03: Volt (Diff) (P2)
1: 1 Reps
2: 5 2500 mV Slow Range ;CR510, CR500 (2500mv); CR23X (1000 mV);
21X, CR7 (5000 mV)
3: 2 DIFF Channel ;Yellow wire (2H), jumper (2L to 1L)
4: 1 Loc [ T_C ]
5: .1 Mult ;See Table 5-1 for alternative multipliers
6: -40 Offset ;See Table 5-1 for alternative offsets
11