Configuring Loggers
Vaisala Veriteq vLog 4.5 41
4
To set up a Voltage channel:
a Ensure the Channel is enabled by selecting the Chan-
nel Enabled
check box.
b If applicable, enter a new channel description.
c If applicable, for Input Range, choose whether this is a
1 or 10 volt range channel.
d From Input Signal, specify the range for your transduc-
er output.
e Under Display Units, specify the range and units to dis-
play instead of the input signal range. For example,
‘psi’ instead of ‘v’.
vLog also supports a Boolean DC Voltage Channel type
on some SP- and VL-4000 loggers. For this type, specify
the Threshold Voltage and the resulting display units. For
example, if you want voltage above the threshold value
to show as 1, indicate 1 for Above Threshold and specify