Chapter 5 ________________________________________ Advanced Use of Lizard Setup Software
VAISALA______________________________________________________________________ 179
Example 5 (Timer Sequence)
Sequence:
- The measurement is executed six times a minute, at 0 s, 10 s, 20 s,
and so on.
- Statistics store each measurement, which is calculated once a
minute, one second after a full minute.
- A report is sent once a minute, two seconds after a full minute.
All timers have the same elements:
- Scale: 1 (absolute)
- Type: 1 (periodic)
Timer 1, measurement:
- Interval: 10000
- Synchronization time: 0
Timer 2, statistics using the measurement as input:
- Intervals: Update 10000, Calculation 60000
- Synchronization time: 1000
Timer 3, reporting using both previous values:
- Interval: 60000
- Synchronization time: 2000
Modifying Timers
Lizard Setup Software provides a single view of timed operations in
which certain topics are only accessible on the Advanced user level.