CHAPTER 3_________________________________________________________________ MOUNTING
VAISALA __________________________________________________________________________ 7
Duct or channel mounting
When the probe is installed in a duct or channel, it is recommended to
use the optional mounting flange (GM45156SP).
1. Drill a hole with minimum diameter of 22 mm in the wall.
2. Attach the flange onto the duct with four screws so that the gasket
ring seals the attachment.
3. Place the probe through the flange so deep that the perforated
head is completely in the duct (see Figure 5).
Figure 5. Mounting the probe in a duct or channel.
NOTE
If the air pressure in the duct is clearly lower than in surroundings, an
additional sealing may be necessary. This is to avoid possible
measurement errors due to leakages through the joint.
Gasket ring