User’s Guide ______________________________________________________________________
42 ___________________________________________________________________ M010056EN-J
Grounding
When grounding the transmitter, follow the local requirements. Use at least
4 mm
2
grounding cable when grounding the transmitter or barrier. Note
that the allowed resistance between barrier and system ground must be less
than 1 ohm. Use ground terminal located inside or outside of transmitter
Figure 21 on page 42:
0505-284
Figure 21 Grounding
HAZARDOUS AREA SAFE AREA