User's Guide _______________________________________________________________________
40 ___________________________________________________________________ M211372EN-D
Set Analog Output Parameters and
Scaling
Use the ASEL command to show or set the output parameters and the
scalings of the analog output.
ASEL [ch1] [ch2]<cr>
Parameter that is output on analog channel 1. Available
parameters are TDF, TDFA, H2O, and P.
Parameter that is output on analog channel 2. Available
parameters the same as for channel 1.
Example (show current settings):
asel
Ch1 Tdf lo : -60.00 'C ?
Ch1 Tdf hi : 40.00 'C ?
Ch2 P lo : 0.00 bara ?
Ch2 P hi : 10.00 bara ?
Example (change output parameters to TDFA and H2O and set scaling):
asel h20 ta
Ch1 Tdfa lo : 00.00 'C ? -80
Ch1 Tdfa hi : 00.00 'C ? 20
Ch2 H2O lo : 0.00 ppm ? 0
Ch2 H2O hi : 0.00 ppm ? 500
Set Analog Output Error Notification
If the transmitter is malfunctioning, the analog output is set to a specified
level. This overrides the normal measurement output of the channel. The
default level is 0 mA or 0V, according to the output type. You can set the
level using the AERR command.
AERR [ch1] [ch2]<cr>
Error level for analog channel 1.
Error level for analog channel 2.
Example (show current settings):
aerr
Ch1 error out : 0.000 mA ?
Ch2 error out : 0.000 V ?
Commentaires sur ces manuels