WXT510 Weather Transmitter
Alias WXT510(6)=Wsmax
Alias WXT510(7)=airtemp
Alias WXT510(8)=relhumidity
Alias WXT510(9)=airpressure
Alias WXT510(10)=Ramount
Alias WXT510(11)=Rduration
Alias WXT510(12)=Rintensity
Alias WXT510(13)=Hamount
Alias WXT510(14)=Hduration
Alias WXT510(15)=Hintensity
'Define Data Tables
DataTable(Table1,True,-1)
DataInterval(0,60,Min,10)
'final data format goes here
Minimum(1,Batt_Volt,FP2,False,False)
EndTable
'Main Program
BeginProg
Scan(15,Sec,1,0)
'Default Datalogger Battery Voltage measurement Batt_Volt:
Battery(Batt_Volt)
'WXT510 SDI-12 Sensor measurements 1-6:
SDI12Recorder(WXT510(1),7,"0","M1!",1,0)
'WXT510 SDI-12 Sensor measurements 7-9:
SDI12Recorder(WXT510(7),7,"0","M2!",1,0)
'WXT510 SDI-12 Sensor measurements 10-15:
SDI12Recorder(WXT510(10),7,"0","M3!",1,0)
'Call Data Tables and Store Data
CallTable(Table1)
NextScan
EndProg