HMP230 SERIES
M210225en-B User's Guide
1
1. PRODUCT DESCRIPTION
The HMP230 series transmitters are microprocessor based instruments for the
measurement of relative humidity and temperature; from these variables they
can calculate dewpoint temperature, absolute humidity, mixing ratio, wet bulb
temperature and enthalpy. The transmitters have two analogue outputs and
they can be connected to a serial bus via the RS 232C interface or through an
RS 485/422 serial module or a current loop module. At dewpoint temperatures
below 0 °C, the user can select whether the transmitter calculates dewpoint or
frostpoint reading; as default, the transmitter calculates dewpoint.
The series consists of four types of transmitters:
HMP231, wall installation
HMP233, ifor tight places; temperatures up to +80 or +120 °C
HMP234, forpressure or vacuum chambers
HMP235, for high temperatures of +180 °C
HMP237, leak proof small size probe for pressures up to 10 bar
HMP238, for pressurized processes
The transmitters can be configured in many ways. They can have either a
blank cover or a cover with a local display and keypad with which the user can
operate the transmitter. The power supply voltage can be selected from three
alternatives. Two analogue output signals are selected from the measured and
calculated quantities; the signals can be scaled and the measurement ranges
changed within certain limits. The HMP233, HMP234, HMP235, HMP237
and HMP238 probes can be supplied with two, five or ten metre sensor head
cable.
The humidity measuring range is 0...100 %RH. The temperature is measured
with a Pt 100 sensor. Temperature measurement range depends on the model;
the HMP234, HMP235, HMP237 and HMP238 have the widest range, -
40...+180 °C. The analogue temperature output can be scaled quite freely, for
example-20...+60 °C can be set to correspond to 0...10 V. The dewpoint
temperature, absolute humidity, mixing ratio, wet bulb temperature and
enthalpy ranges are also scalable.
In some applications the sensor gain may gradually decrease because of an
interference caused by some chemical present in the ambient. These changes
can be recovered with an optional re-gaining function. Transmitters including
this function are equipped with a composite humidity and temperature sensor.
The HMP230 series units incorporate the HUMICAP
®
sensor, which uses an
operating principle based on changes in the capacitance of the sensor as its
thin polymer film absorbs water molecules.