Table 12 ALSEL Parameters
If specified, the alarm goes off when the quantity value rises above
the exact value of this setpoint. However, if above < below, the
alarm goes off at (above + hyst) and (below – hyst) instead.
Cannot be set for fault and online alarms.
If specified, the alarm goes off when the quantity value decreases
below the exact value of this setpoint. However, if above < below,
the alarm goes off at (above + hyst) and (below – hyst) instead.
Cannot be set for fault and online alarms.
Distance from setpoint amount of extra retractment needed in order
to regenerate alarm on the next crossing of the setpoint.
Cannot be set for fault and online alarms.
Enable (ON) or disable (OFF) the display alarm.
Example (set H2O and T as display alarm quantities and configure the
alarms as prompted):
>alsel h2o t
Al1 H2O above: 0.00 ppmV ? 6000
Al1 H2O below: - ?
Al1 H2O hyst : 1.00 ppmV ? 500
Al1 H2O enabl: ON ?
Al2 T above: 40.00 'C ? 30
Al2 T below: - ?
Al2 T hyst : 1.00 'C ?
Al2 T enabl: ON ?
>